Diagnostic messages
246
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Error group 28
Operating hour counter
No.
Reaction
Message
Code
28-2
FF03h
Operating hour counter corrected
configurable
Cause
The operating hour counter has a backup copy. If the controller's
24 V power supply fails precisely when the operating hour counter
is being updated, the written record may be corrupted. In such
cases, the controller restores the operating hour counter from the
intact backup copy when it switches back on.
Measure
Warning only, no further action required.
28-3
FF04h
Operating hour counter converted
configurable
Cause
Firmware was loaded in which the operating hour counter has a
different data format. The next time the controller is switched on,
the old operating hour counter record is converted to the new
format.
Measure
Warning only, no further action required.
Error group 29
Memory card
No.
Code
Message
Reaction
29-0
-
Memory card not available
configurable
Cause
This error is triggered in the following cases:
–
If an action should be carried out on the memory card (load or
create DCO file, firmware download), but no memory card is
plugged in.
–
The DIP switch S3 is set to ON, but no card is plugged in after
the reset/restart.
Measure
Insert appropriate memory card in the slot.
Only if expressly desired!
29-1
-
Memory card: Initialisation error
configurable
Cause
This error is triggered in the following cases:
–
Memory card could not be initialised. Card type may not be
supported!
–
File system not supported.
–
Error in connection with the shared memory.
Measure
Check card type used.
Connect memory card to a PC and format again.