Chapter 10
Serial Server
RUGGEDCOM ROX II
CLI User Guide
334
Configuring the Modbus TCP Protocol
Parameter
Description
aging-timer { aging-timer }
Synopsis:
A 32-bit signed integer between 60 and 10800
Default:
1000
The length of time a learned DNP device in the Device Address Table may go without any
DNP communication before it is removed from the table.
max-connection { max-connection }
Synopsis:
A 32-bit signed integer between 1 and 32
Default:
1
The maximum number of incoming DNP connections.
4. Add a Device Address table. For more information about adding Device Address tables, refer to
Section 10.3.2, “Adding a Device Address Table”
.
5. Type
commit
and press
Enter
to save the changes, or type
revert
and press
Enter
to abort.
Section 10.2.5
Configuring the Modbus TCP Protocol
To configure the modbus TCP protocol for a serial port, do the following:
1. Make sure the CLI is in Configuration mode.
2. Navigate to
interface » serial » {interface} » protocols » tcpmodbus » settcpmodbus
, where
{interface}
is
the serial port.
3. Configure the following parameter(s) as required:
Parameter
Description
response-timer { response-timer }
Synopsis:
A 32-bit signed integer between 50 and 10000
Default:
100
The maximum time from the last transmitted character of the outgoing poll until the
first character of the response. If the RTU does not respond in this time, the poll will have
been considered failed.
pack-timer { pack-timer }
Synopsis:
A 32-bit signed integer between 5 and 1000
Default:
1000
The maximum allowable time to wait for a response to a Modbus request to complete
once it has started.
turnaround { turnaround }
Synopsis:
A 32-bit signed integer between 0 and 1000
Default:
0
The amount of delay (if any) to insert after the transmissions of Modbus broadcast
messages out the serial port.
retransmit { retransmit }
Synopsis:
A 32-bit signed integer between 0 and 2
Default:
0
The number of times to retransmit the request to the RTU before giving up.
max-connection { max-connection }
Synopsis:
A 32-bit signed integer between 1 and 32
Default:
1
The maximum number of incoming connections.
local-port { local-port }
Synopsis:
A 32-bit signed integer
Default:
502
The alternate local TCP port number. If this field is configured, a single connection
(per serial port) may be made to this alternate port number. Note that Modbus TCP
uses a default local port number of 502. There is no limit imposed on the number of
connections to the default TCP port.
Summary of Contents for RUGGEDCOM ROX II
Page 2: ...RUGGEDCOM ROX II CLI User Guide ii ...
Page 4: ...RUGGEDCOM ROX II CLI User Guide iv ...
Page 39: ...RUGGEDCOM ROX II CLI User Guide Table of Contents xxxix 19 5 VLANs 752 ...
Page 40: ...Table of Contents RUGGEDCOM ROX II CLI User Guide xl ...
Page 46: ...Preface RUGGEDCOM ROX II CLI User Guide xlvi Customer Support ...
Page 170: ...Chapter 5 System Administration RUGGEDCOM ROX II CLI User Guide 124 Deleting a Scheduled Job ...
Page 256: ...Chapter 6 Security RUGGEDCOM ROX II CLI User Guide 210 Enabling Disabling a Firewall ...
Page 402: ...Chapter 11 Wireless RUGGEDCOM ROX II CLI User Guide 356 Managing Cellular Modem Profiles ...