Exchanging Data with the CPU Unit
Section 4-5
Set Values and Stored Values
Allocation for Adjustment
Mode
For adjustment mode, set the operation mode switch on the rear panel of the
Unit as shown in the following diagram. When the Unit is set for adjustment
mode, the ADJ indicator on the front panel of the Unit will flash.
The allocation of CIO words and bits is shown in the following table.
Note
1.
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
2.
The range is 1 to 4 for the CS1W-DA04.
I/O
Item
Contents
Page
Output
Conversion enable
0: Conversion output stopped.
1: Conversion output begun.
Set value
16-bit binary data
Output setting error
0: No error
1: Output setting error
Common
Alarm Flags
Bits 00 to 03: Output set value error
Bits 04 to 09: Not used
Bit 10:
Output hold setting error
Bit 11:
Not used
Bit 15:
Operating in adjustment mode
(always 0 in normal mode)
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Not used.
Outputs to be adjusted
2 (fixed)
1 to 8 (See note 2.)
n + 1
Not used.
Not used.
Clr
Set
Up
Down
Gain Off-
set
n + 2
Not used.
n + 3
Not used.
n + 4
Not used.
n + 5
Not used.
n + 6
Not used.
n + 7
Not used.
Input
(Unit to
CPU)
n + 8
Conversion value or set value at time of adjustment
16
3
16
2
16
1
16
0
n + 9
Alarm Flags
Not used.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......