14
Specifications
Section 2-1
2-1
Specifications
2-1-1
Specifications
Item
CS1W-AD041-V1
CS1W-AD081-V1
CS1W-AD161
Unit type
CS-series Special I/O Unit
Isolation (See note 1.)
Between I/O and PLC signals: Photocoupler
(No isolation between individual I/O signals.)
External terminals
21-point detachable terminal block (M3 screws)
Two 34-pin MIL connectors
Affect on CPU Unit cycle time
0.2 ms
Power consumption
120 mA max. at 5 VDC, 90 mA max. at 26 VDC
150 mA max. at 5 VDC,
55 mA max. at 26 VDC
Dimensions (mm) (See note 2.)
35 x 130 x 126 (W x H x D)
35 x 130 x 119 (W x H x D)
Weight
450 g max.
General specifications
Conforms to general specifications for SYSMAC CS Series.
Mounting position
CS-series CPU Rack or CS-series Expansion Rack
(Cannot be mounted to a C200H Expansion I/O Rack or a SYSMAC BUS Slave
Rack.)
Maximum number of Units
(See note 3.)
Refer to the table on page 15.
Data exchange with CPU Units
(See note 4.)
Special I/O Unit Area in CIO Area (CIO 2000 to CIO
2959): 10 words per Unit
Special I/O Unit Area in DM Area (D20000 to D29599):
100 words per Unit
Special I/O Unit Area in
CIO Area (CIO 2000 to
CIO 2959): 20 words per
Unit
Special I/O Unit Area in
DM Area (D20000 to
D29599): 200 words per
Unit
Input
specifi-
cations
Number of analog inputs
4
8
16
Input signal range
(See note 5.)
1 to 5 V
0 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
(See note 6.)
Maximum rated input (for
1 point) (See note 7.)
Voltage Input:
±
15 V
Current Input:
±
30 mA
Input impedance
Voltage Input: 1 M
Ω
min.
Current Input: 250
Ω
(rated value)
Resolution
4,000/8,000 (See note 8.)
Converted output data
16-bit binary data
Accuracy
(See note
9.)
23
±
2
°
C
Voltage Input:
±
0.2% of full scale
Current Input:
±
0.4% of full scale
Voltage Input:
±
0.2% of full
scale
Current Input:
±
0.2% of full
scale
0
°
C to 55
°
C Voltage Input:
±
0.4% of full scale
Current Input:
±
0.6% of full scale
Voltage Input:
±
0.4% of full
scale
Current Input:
±
0.4% of full
scale
A/D conversion time
(See note 10.)
1.0 ms or 250
µ
s per point max. (See note 8.)
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......