52
Analog Input Functions and Operating Procedures
Section 2-6
2-6
Analog Input Functions and Operating Procedures
2-6-1
Input Settings and Conversion Values
Input Numbers
The Analog Input Unit converts analog inputs specified by input numbers. To
specify the analog inputs to be used, turn ON from a Programming Device the
D(m) bits in the DM Area shown in the following diagram.
Setting 0: Not used.
1: Used
• CS1W-AD041-V1: Inputs 1 to 4
• CS1W-AD081-V1: Inputs 1 to 8
The analog input sampling interval can be shortened by setting any unused
input numbers to 0.
Sampling interval = (1 ms) x (Number of inputs used) (See note.)
Note
Use 250
µ
s instead of 1 ms is set to a conversion time of 250
µ
s and
resolution of 8,000.
The conversion values in words for inputs that have been set to “Not used” will
always be “0000.”
For the DM word addresses, m = (unit number x 100)
Input Signal Range
Any of four types of input signal range (–10 to 10 V, 0 to 10 V, 1 to 5 V, and 4
to 20 mA) can be selected for each of the inputs.
CS1W-AD041-V1/AD081-V1
To specify the input signal range for each input, set from a Programming
Device the D(m + 1) bits in the DM Area as shown in the following diagram.
Note
There are only four inputs for the CS1W-AD041-V1.
CS1W-AD161
D(m)
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
m = unit number x 100
Input 2
Input 1
Input 4
Input 3
Input 6
Input 5
Input 8
Input 7
Input 10
Input 9
Input 12
Input 11
Input 14
Input 13
Input 16
Input 15
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Bit
DM (m+1)
Input 2
Input 1
00:
−
10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA
11: 0 to 5 V
Input 4
Input 3
Input 6
Input 5
Input 8
Input 7
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
D (m+1)
Input 8
Input 6
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
D (m+2)
Input 16
Input 15
Input 14
Input 13
Input 12
Input 11
Input 10
Input 9
m = unit number x 100
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......