21
Operating Procedure
Section 2-2
select either voltage input or current input by wiring the connector termi-
nals. Use DM word m+52 to select 1 to 5 V or 4 to 20 mA as the voltage or
current input range, respectively.
3.
Setting the Unit Number
Set the unit number for the Special I/O Unit using the rotary switches on
the front panel of the Unit.
Set the CS1W-AD041-V1 and CS1W-AD081-V1 between 0 and 95. A sin-
gle CS1W-AD161 is allocated words in the CIO Area and DM Area for two
Units. Set the unit number between 0 and 94. To set a CS1W-AD161 to unit
number "n," the unit number setting "n+1" is not possible.
2-2-1
Procedure Examples
The procedure for using Analog Input Units is provided here using the CS1W-
AD081-V1 as an example. The method used to set CS1W-AD161 Analog
Input Units is different. Be sure to use the correct procedure.
Setting the Analog Input Unit
1,2,3...
1.
Set the operation mode. Refer to
for further
details.
The operation mode can be changed by setting DM word m+18 (DM word
m+19 for CS1W-AD161).
CS1W-AD081-V1
CS-series CPU Unit
Unit No.: 1
Analog input
IN5: 0 to 10 V
IN6: 0 to 10 V
IN7: –10 to 10 V
IN8: Not used
IN1: 1 to 5 V
IN2: 1 to 5 V
IN3: 4 to 20 mA
IN4: 4 to 20 mA
Ladder Program
Turn OFF SW1 for normal mode
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......