314
Exchanging Data with the CPU Unit
Section 7-5
Set Values and Stored Values
Note
1.
The input signal range of “1 to 5 V” and “4 to 20 mA” is switched using the
pins of the voltage/current switch. Refer to
for
details.
2.
For the range of
±
10 V, the output is 0 V. For other output signal ranges,
the minimum value of each signal range is output. Refer to
for details.
3.
The default setting for mean value processing is to use two buffers.
Item
Contents
Page
Input
Use setting
0:
Not used.
1:
Used.
Input signal range
00: –10 to 10 V
01: 0 to 10 V
10: 1 to 5 V, 4 to 20 mA (See note 1.)
11: 0 to 5 V
Voltage/current range setting 0: Voltage range (1 to 5 V)
1: Current range (4 to 20 mA)
Mean value processing set-
ting
0000: Mean value processing for 2 buffers (See note 3.)
0001: No mean value processing
0002: Mean value processing for 4 buffers
0003: Mean value processing for 8 buffers
0004: Mean value processing for 16 buffers
0005: Mean value processing for 32 buffers
0006: Mean value processing for 64 buffers
Scaling setting
Set any value in binary data from -32,000 (8,300) to +32,000 (7D00), except
when upper limit = lower limit (not 0000).
Output
Use setting
0:
Not used.
1:
Used.
Output signal range
00: –10 to 10 V
01: 0 to 10 V
10: 1 to 5 V
11: 0 to 5 V
Voltage/current range setting 0: Voltage range (1 to 5 V)
1: Current range (4 to 20 mA)
Output status when stopped
00: CLR
Outputs 0 or minimum value of each range.
(See note 2.)
01: HOLD
Holds output just before stopping.
02: MAX
Outputs maximum value of range.
Scaling setting
Set any value in binary data from
−
32,000 (8,300) to +32,000 (7D00), except
when upper limit = lower limit (not 0000).
Loop
Ratio conversion use setting
00: Not used.
01: Uses positive gradient conversion.
10: Uses negative gradient conversion.
11: Same as for setting “00” above.
A constant
4 digits BCD (0 to 9999)
B constant
16-bit binary data
Conversion time/resolution setting (for
inputs and outputs)
00: Conversion time of 1 ms and resolution of 4,000
C1: Conversion time of 500
µ
s and resolution of 8,000
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......