Analog Input Functions and Operating Procedures
Section 2-6
00:
−
10 to +10 V
01: 0 to 10 V
10: 1 to 5 V/4 to 20 mA (See note 2.)
11: 0 to 10 V
Select the input signal range 1 to 5 V/4 to 20 mA by wiring the connector or
terminal block conversion connector. The voltage/current input setting can
also be set using DM word m+52.
0: 1 to 5 V
1: 4 to 20 mA
Note
1.
For the DM word addresses, m = (unit number x 100)
2.
The input signal range of “1 to 5 V” or “4 to 20 mA” is switched using the
voltage/current switch.
3.
After making the DM settings from a Programming Device, it will be neces-
sary to either turn the power to the PLC OFF and ON, or turn ON the Spe-
cial I/O Unit Restart Bit in order to transfer the contents of the DM settings
to the Special I/O Unit.
Reading Conversion
Values
Analog input conversion values are read in 4-digit hexadecimal for each input.
Note
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
Use MOV(021) or XFER(070) to read conversion values in the user program.
Example 1
In this example, the conversion data from only one input is read. (The unit
number is 0.)
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
D (m+52)
Input
16
Input
15
Input
14
Input
13
Input
12
Input
11
Input
10
Input
9
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
m = unit number x 100
Address
CS1W-AD161
CS1W-AD081-V1
CS1W-AD041-V1
n+1
Input 1 conversion value
Input 1 conversion value
Input 1 conversion value
n+2
Input 2 conversion value
Input 2 conversion value
Input 2 conversion value
n+3
Input 3 conversion value
Input 3 conversion value
Input 3 conversion value
n+4
Input 4 conversion value
Input 4 conversion value
Input 4 conversion value
n+5
Input 5 conversion value
Input 5 conversion value
Cannot be used.
n+6
Input 6 conversion value
Input 6 conversion value
n+7
Input 7 conversion value
Input 7 conversion value
n+8
Input 8 conversion value
Input 8 conversion value
n+9
Input 9 conversion value
Cannot be used.
n+10
Input 0 conversion value
n+11
Input 1 conversion value
n+12
Input 12 conversion value
n+13
Input 13 conversion value
n+14
Input 14 conversion value
n+15
Input 15 conversion value
n+16
Input 16 conversion value
MOV(021)
2001
D00001
Input condition
Conversion data in CIO word
2001 (input number 1) is read
to D 00001.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......