45
Exchanging Data with the CPU Unit
Section 2-5
Note
For the DM word addresses, m = (unit number x 100).
Set Values and Stored Values
Note
1.
For CS1W-AD041-V1 and CS1W-AD081-V1, the input signal range of “1
to 5 V” and “4 to 20 mA” is switched using the pins of the voltage/current
switch. Refer to
2-3-4 Voltage/Current Switch (CS1W-AD041-V1/AD081-
for details. With CS1W-AD161, select voltage/current input by wiring
the connector terminals.
2.
The default of mean value processing setting is set to “Mean value pro-
cessing for 2 buffers.” Refer to
3.
Voltage/current input selection can be set for input signal ranges of 1 to 5 V
and 4 to 20 mA using the switch at the back of the terminal block for CS1W-
AD041-V1 and CS1W-AD081-V1, or selected when wiring the connector
or in DM word m+52 for CS1W-AD161.
D(m+42)
Input 12 scaling lower limit
D(m+43)
Input 12 scaling upper limit
D(m+44)
Input 13 scaling lower limit
D(m+45)
Input 13 scaling upper limit
D(m+46)
Input 14 scaling lower limit
D(m+47)
Input 14 scaling upper limit
D(m+48)
Input 15 scaling lower limit
D(m+49)
Input 15 scaling upper limit
D(m+50)
Input 16 scaling lower limit
D(m+51)
Input 16 scaling upper limit
D(m+52)
Voltage/current range setting (Only for 1 to 5 V and 4 to 20 mA.)
Input
16
Input
15
Input
14
Input
13
Input
12
Input
11
Input
10
Input
9
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
Item
Contents
Page
Input
Use setting
0:
Not used.
1:
Used.
Input signal range
00:
–10 to 10 V
01:
0 to 10 V
10:
1 to 5 V/4 to 20 mA (See note 1.)
11:
0 to 5 V
Mean value processing set-
ting
0000:
Mean value processing for 2 buffers (See note 3.)
0001:
No mean value processing
0002:
Mean value processing for 4 buffers
0003:
Mean value processing for 8 buffers
0004:
Mean value processing for 16 buffers
0005:
Mean value processing for 32 buffers
0006:
Mean value processing for 64 buffers
Scaling setting
Only set for CS1W-AD161
DM word
(See note
1.)
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......