
236
Operating Procedure
Section 6-2
Note a)
The addresses are set according to the unit number of the Special
I/O Unit. Refer to
for further details.
b)
Set as required.
D00200 is set in word CIO 2011.
D00201 is set in word CIO 2012.
D00202 is set in word CIO 2013.
The data in words CIO 2011 and CIO
2012 will be output as 1 to 5 V, and
the data in CIO 2013 will be output as
–10 to 10 V.
To start analog output, turn ON the
Conversion Enable Bits 201000 to
201002 (bits 00 to 02 of word
CIO 2010).
MOV (021)
D00200
2011
MOV (021)
D00201
2012
Execution condition
MOV (021)
D00202
2013
SET
201000
SET
201002
SET
201001
Execution condition
See
on page 260 for details.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......