69
Handling Errors and Alarms
Section 2-8
While the Clear Bit is ON, the adjusted value will be cleared and reset to
the default offset and gain values when the Set Bit turns ON.
3.
To finish the clearing of adjusted values, turn OFF bit 05 (the Clear Bit) of
CIO word n+1.
!Caution
Do not turn OFF the power supply or restart the Unit while the Set Bit is ON
(data is being written to the EEPROM). Otherwise, illegal data may be written
in the Unit’s EEPROM and “EEPROM Errors” may occur when the power sup-
ply is turned ON or when the Unit is restarted, causing a malfunction.
!Caution
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment at the same time.
Note
The EEPROM can be overwritten 50,000 times.
2-8
Handling Errors and Alarms
2-8-1
Indicators and Error Flowchart
Indicators
If an alarm or error occurs in the Analog Input Unit, the ERC or ERH indica-
tors on the front panel of the Unit will light.
SHIFT
CONT
#
2
C
0
A
0
A
1
B
0
A
5
F
MON
200105 ^ ON
RESET
200105 ^ OFF
LED
Meaning
Indicator
Operating status
RUN (green) Operating
Lit
Operating in normal mode.
Not lit
Unit has stopped exchanging data with
the CPU Unit.
ERC (red)
Unit has
detected an
error
Lit
Alarm has occurred (such as disconnec-
tion detection) or initial settings are incor-
rect.
Not lit
Operating normally.
ADJ (yellow) Adjusting
Flashing
Operating in offset/gain adjustment
mode.
Not lit
Other than the above.
ERH (red)
Error in the
CPU Unit
Lit
Error has occurred during data exchange
with the CPU Unit.
Not lit
Operating normally.
Front panel of Unit
RUN
ERC
ADJ
ERH
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......