202
Analog Output Functions and Operating Procedures
Section 5-6
generated and scaling cannot be executed. Operation starts normally
when both the upper and lower limits are set to 0000 (the default values).
Setting Upper and Lower
Limits for Output Scaling
Set the scaling upper and lower limits for outputs 1 and 2 in words D(m+19) to
D(m+22) of the DM Area, as shown below.
Note
For decimal numbers
−
32,000 to +32,000, set 16-bit binary data (8300 to
7D00).
Example Setting 1
Set the following conditions in D(m+19) to D(m+22). (The values shown in
parentheses are binary data.)
When Output Signal Range is 0 V to 10 V
The following table shows the correspondence between output signals and
converted scaling values. (The values shown in parentheses are 16-bit binary
data.)
Example Setting 2
(Reverse Scaling)
Set the following conditions in D(m+27) to D(m+34). (The values shown in
parentheses are binary data.)
DM word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
D(m+19)
Output 1 scaling lower limit
D(m+20)
Output 1 scaling upper limit
D(m+21)
Output 2 scaling lower limit
D(m+22)
Output 2 scaling upper limit
Setting condition
Set value
Output signal range
0 to 10 V
Scaling lower limit
0000 (0000)
Scaling upper limit
10,000 (2710)
Output set value
Output signal
0000 (0000)
0 V
10,000 (2710)
10 V
−
500 (FE0C)
−
0.5 V
10,500 (2904)
10.5 V
+10.5 V
+10 V
0 V
−
0.5 V
0000 (0000)
−
500 (FE0C)
Scaling line
10500 (2904)
10000 (2710)
Setting condition
Set value
Output signal range
0 to 10 V
Scaling lower limit
10,000 (2710)
Scaling upper limit
0000 (0000)
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......