Exchanging Data with the CPU Unit
Section 2-5
2-5-2
Unit Number Settings
The Special I/O Unit Area and Special I/O Unit DM Area word addresses that
each Analog Input Unit occupies are set by the unit number switch on the front
panel of the Unit.
Note
1.
If two or more Special I/O Units are assigned the same unit number, a
“UNIT No. DPL ERR” error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
2.
Be sure to set a unit number such that the CS1W-AD161 is not allocated
words in the CIO Area and DM Area that are already allocated to other
Special I/O Units. The unit number can be set between 0 and 94.
Switch
setting
CS1W-AD041-V1/AD081-V1
CS1W-AD161 (See note 2.)
Unit
number
Special/O Unit Area
addresses
Special I/O Unit DM
Area addresses
Unit
number
Special/O Unit Area
addresses
Special I/O Unit DM
Area addresses
0
Unit #0
CIO 2000 to
CIO 2009
D20000 to D20099
Unit #0
CIO 2000 to
CIO 2019
D20000 to D20199
1
Unit #1
CIO 2010 to
CIO 2019
D20100 to D20199
Unit #1
CIO 2010 to
CIO 2029
D20100 to D20299
2
Unit #2
CIO 2020 to
CIO 2029
D20200 to D20299
Unit #2
CIO 2020 to
CIO 2039
D20200 to D20399
3
Unit #3
CIO 2030 to
CIO 2039
D20300 to D20399
Unit #3
CIO 2030 to
CIO 2049
D20300 to D20499
4
Unit #4
CIO 2040 to
CIO 2049
D20400 to D20499
Unit #4
CIO 2040 to
CIO 2059
D20400 to D20599
5
Unit #5
CIO 2050 to
CIO 2059
D20500 to D20599
Unit #5
CIO 2050 to
CIO 2069
D20500 to D20699
6
Unit #6
CIO 2060 to
CIO 2069
D20600 to D20699
Unit #6
CIO 2060 to
CIO 2079
D20600 to D20799
7
Unit #7
CIO 2070 to
CIO 2079
D20700 to D20799
Unit #7
CIO 2070 to
CIO 2089
D20700 to D20899
8
Unit #8
CIO 2080 to
CIO 2089
D20800 to D20899
Unit #8
CIO 2080 to
CIO 2099
D20800 to D20999
9
Unit #9
CIO 2090 to
CIO 2099
D20900 to D20999
Unit #9
CIO 2090 to
CIO 2109
D20900 to D21099
10
Unit #10
CIO 2100 to
CIO 2109
D21000 to D21099
Unit #10
CIO 2100 to
CIO 2119
D21000 to D21199
~
~
~
~
~
~
~
n
Unit #n
CIO 2000 + (n x 10)
to CIO 2000 + (n x
10) + 9
(n x 100)
to
(n x 100) +
99
Unit #n
CIO 2000 + (n x 10)
to CIO 2000 + (n x
10) + 19
(n x 100)
to
(n x 100) +
199
~
~
~
~
~
~
~
94
Unit #94
CIO 2940 to
CIO 2949
D29400 to D29499
Unit #94
CIO 2940 to
CIO 2959
D29400 to D29499
95
Unit #95
CIO 2950 to
CIO 2959
D29500 to D29599
Not
used.
---
---
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......