Specifications
Section 4-1
4-1-2
Output Function Block Diagram
Note
There are only four analog outputs for the CS1W-DA041.
4-1-3
Output Specifications
If the set value is outside the specified range provided below, an output setting
error will occur, and the output specified by the output hold function will be
output.
Range: 1 to 5 V (4 to 20 mA)
Analog Output Unit
CPU Unit
Special I/O
Unit Area
Analog
output 1
set value
Output hold
enabled
Output hold
disabled
D/A
Analog output 1
Same as above.
Analog output 2
Same as above.
Analog output 3
Same as above.
Analog output 4
Same as above.
Analog output 5
Same as above.
Analog output 7
Same as above.
Analog output 8
Same as above.
Analog output 6
5.2 V (20.8 mA)
5 V (20 mA)
1 V (4 mA)
0.8 V (3.2 mA)
0000
FF38
0FA0
1068
Resolution: 4,000
Set value (16-bit binary data)
Analog output signal