357
Handling Errors and Alarms
Section 7-10
Value Does Not Change as Intended
Conversion Values are Inconsistent
Analog Output Does Not Change
Output Does Not Change as Intended
Outputs are Inconsistent
Probable cause
Countermeasure
Page
The input device’s signal range
does not match the input signal
range for the relevant input number
at the Analog I/O Unit.
Check the specifications of the
input device, and match the settings
for the input signal ranges.
The offset and gain are not
adjusted.
Adjust the offset and gain.
When using the 4 mA to 20 mA
range, the voltage/current switch is
not turned ON.
Turn ON the voltage/current switch.
The voltage and current ranges are
not set in D(m+35).
Set D(m+35) correctly.
The ratio conversion function is set
to be used, so the calculation
results are being monitored.
Correct the conversion settings.
Probable cause
Countermeasure
Page
The input signals are being affected
by external noise.
Change the shielded cable connec-
tion to the Unit’s COM terminal.
Insert a 0.01-
µ
F to 0.1-
µ
F ceramic
capacitor or film capacitor between
the input’s (+) and (–) terminals.
---
Try increasing the number of mean
value processing buffers.
Probable Cause
Countermeasure
Page
The output is not set for being used. Set the output to be used.
The output hold function is in opera-
tion.
Turn ON the Output Conversion
Enable Bit.
The conversion value is set outside
of the permissible range.
Set the data within the range.
Probable Cause
Countermeasure
Page
The output signal range setting is
wrong.
Correct the output signal range set-
ting.
The I/O specifications of the output
device do not match those of the
Analog I/O Unit (e.g., input signal
range, input impedance).
Change the output device.
The offset or gain is not adjusted.
Adjust the offset or gain.
The voltage and current ranges are
not set in D(m+35).
Set D(m+35) correctly.
The ratio conversion function is set
to be used.
Correct the conversion settings.
Probable Cause
Countermeasure
Page
The output signals are being
affected by external noise.
Try changing the shielded cable
connection (e.g., the grounding at
the output device).
---
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......