99
Exchanging Data with the CPU Unit
Section 3-5
3-5-4
Fixed Data Allocations
DM Allocation and
Contents
The initial settings of the Analog Input Unit are set according to the data allo-
cated in the Special I/O Unit DM Area. Settings, such as the inputs used and
the analog input signal range must be set in this area.
The conversion time and resolution can be set, along with the operation
mode, in DM word m+18.
Note
1.
The Special I/O Unit DM Area words that are occupied by the Analog Input
Unit are set using the unit number switch on the front panel of the Unit. Re-
fer to
for details on the method used to set the
unit number switch.
2.
If two or more Special I/O Units are assigned the same unit number, a
“UNIT No. DPL ERR” error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
3.
Only D(m) to D(m+5) are supported by the CJ1W-AD041-V1.
D(m+1)
D(m)
D20300 to D20399
D20400 to D20499
D20500 to D20599
D20000 to D20099
D20100 to D20199
D20200 to D20299
D20900 to D20999
D20600 to D20699
D20700 to D20799
D20800 to D20899
SYSMAC CJ-series CPU Unit
CJ1W-AD041-V1/081-V1 Analog Input Unit
(Fixed Data Area)
Unit #0
Unit #1
Unit #2
Unit #3
Unit #4
Unit #5
Unit #6
Unit #7
Unit #8
Unit #9
(Special I/O Unit DM Area)
Word
D29500 to D29599
D21000 to D21099
~
Unit #10
~
Unit #n
~
Unit #95
Input signal range
m = 20000 + (unit number x 100)
~
(n x 100) to
(n x 100) + 99
Data is automatically
transferred to each unit
number when the power
is turned ON, or when
the Special I/O Unit
Restart Bit is turned ON.
Input conversion
permission loop
mode setting
D(m+2 to
m+9)
(See note
3.)
Sets number of
samplings for mean
value processing
Conversion time/
resolution and
operation mode
D(m+18)
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......