163
Handling Errors and Alarms
Section 4-8
4-8
Handling Errors and Alarms
4-8-1
Indicators and Error Flowchart
Indicators
If an alarm or error occurs in the Analog Output Unit, the ERC or ERH indica-
tors on the front panel of the Unit will light.
Troubleshooting
Procedure
Use the following procedure for troubleshooting Analog Output Unit errors.
LED
Meaning
Indicator
Operating status
RUN (green) Operating
Lit
Operating in normal mode.
Not lit
Unit has stopped exchanging data with
the CPU Unit.
ERC (red)
Unit has
detected an
error
Lit
Alarm has occurred (such as disconnec-
tion detection) or initial settings are incor-
rect.
Not lit
Operating normally.
ADJ (yellow) Adjusting
Flashing
Operating in offset/gain adjustment
mode.
Not lit
Other than the above.
ERH (red)
Error in the
CPU Unit
Lit
Error has occurred during data exchange
with the CPU Unit.
Not lit
Operating normally.
Front panel of Unit
RUN
ERC
ADJ
ERH
Is the ERC indicator
lit?
Yes
No
Is the RUN indicator
lit?
Yes
No
Alarm has occurred at the Analog Output Unit.
Check whether the initial settings for the Analog Output
Unit are set correctly.
Is the ERH indicator
lit?
Yes
No
Is the RUN indicator
lit?
Yes
No
Error detected by CPU Unit
Check whether the unit number is set correctly.
Error occurs.
(Refer to
4-8-2 Alarms Occurring at the Analog Output
(Refer to
4-8-2 Alarms Occurring at the Analog Output
.)
(Refer to
(Refer to
Refer to
.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......