154
Adjusting Offset and Gain
Section 4-7
The following diagram shows the flow of operations when using the adjust-
ment mode for adjusting offset and gain.
!Caution
Be sure to turn OFF the power to the PLC before changing the setting of the
operation mode switch.
Set the operation mode switch to adjustment mode.
Turn ON the PLC.
When adjusting another output number
When adjusting the same output number
Set the output number.
Offset adjustment
Offset Bit ON
Set Bit ON
Turn OFF power to the PLC.
Set the operation mode switch to adjustment mode.
The ADJ indicator will flash while in adjustment mode.
Gain adjustment
Gain Bit ON
Output adjustment
Set Bit ON
Output adjustment
Set the operation mode switch on the rear panel
of the Unit to normal model
(Bit 4 of CIO word
n+1 turns ON.)
(Bits 2 and 3 of
CIO word n+1
turn ON.)
Adjustment
value setting
(Bit 0 of CIO word
n+1 turns ON.)
(Bit 4 of CIO word
n+1 turns ON.)
(Bits 2 and 3 of
CIO word n+1
turn ON.)
Adjustment
value setting
(Bit 1 of CIO word
n+1 turns ON.)
Write the output number to be adjusted
in the rightmost byte of CIO word n.
Start up the PLC in PROGRAM mode.
Set the operation mode switch on the rear panel of
the Unit to adjustment mode.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......