49
Exchanging Data with the CPU Unit
Section 2-5
CS1W-AD161
Note
For the CIO word addresses, n = CIO 2000 + unit number x 10.
Set Values and Stored Values
The input disconnection detection function can be used when the input signal
range is set for 1 to 5 V (4 to 20 mA).
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Peak value hold
Input
16
Input
15
Input
14
Input
13
Input
12
Input
11
Input
10
Input
9
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
Input
(Unit to
CPU)
n + 1
Input 1 A/D conversion value
16
3
16
2
16
1
16
0
n + 2
Input 2 A/D conversion value
n + 3
Input 3 A/D conversion value
n + 4
Input 4 A/D conversion value
n + 5
Input 5 A/D conversion value
n + 6
Input 6 A/D conversion value
n + 7
Input 7 A/D conversion value
n + 8
Input 8 A/D conversion value
n + 9
Input 9 A/D conversion value
n + 10
Input 10 A/D conversion value
n + 11
Input 11 A/D conversion value
n + 12
Input 12 A/D conversion value
n + 13
Input 13 A/D conversion value
n + 14
Input 14 A/D conversion value
n + 15
Input 15 A/D conversion value
n + 16
Input 16 A/D conversion value
n + 17
Not used.
n + 18
Disconnection detection
Input
16
Input
15
Input
14
Input
13
Input
12
Input
11
Input
10
Input
9
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
n + 19
Alarm flags
Not used.
I/O
Item
Contents
Page
Output
Peak value hold function
0:
Not used.
1:
Peak value hold used.
Common
Conversion value
(calculation result)
4-digit hexadecimal
Disconnection detection
0:
No disconnection
1:
Disconnection
Alarm Flags
• CS1W-AD041-VI and CS1W-AD081-V1: CIO n+9
Bit 11: Mean value processing setting error
Bit 15: Operating in adjustment mode (always OFF in normal mode)
• CS1W-AD161: CIO n+19
Bit 08: Scaling data setting error
Bit 11: Mean value processing setting error
Bit 12: Conversion time/resolution or operation mode setting error
Bit 15: Operating in adjustment mode (always OFF in normal mode)
Input signal range
Voltage/current
1 to 5 V
0.3 V max.
4 to 20 mA
1.2 mA max.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......