Handling Errors and Alarms
Section 2-8
The unit number for the Analog Input Unit has not been set correctly.
Note
A single CS1W-AD161 is allocated CIO Area and DM Area words for two Spe-
cial I/O Units. Be sure to set a unit number so that the CS1W-AD161 is not
allocated words in the CIO Area and DM Area that are already allocated to
other Special I/O Units. Unit numbers for CS1W-AD161 can be set from 0 to
94.
2-8-4
Restarting Special I/O Units
There are two ways to restart Special I/O Unit operation after having changed
DM contents or having cleared the cause of an error. The first way is to turn
the power to the PLC OFF and ON, and the second way is to turn ON the
Special I/O Unit Restart Bit.
Special I/O Unit Restart Bits
The conversion data becomes 0000 during restart.
If the error is not cleared even after turning the Special I/O Unit Restart Bit ON
and then OFF again, then replace the Unit.
Note
The highest unit number that can be set for a CS1W-AD161 is unit number 94.
2-8-5
Troubleshooting
The following tables explain the probable causes of troubles that may occur,
and the countermeasures for dealing with them.
Conversion Data Does Not Change
Error
Error contents
Input status
Duplicate Unit Number
(See note.)
The same unit number has been
assigned to more than one Unit
or the unit number was set to a
value other than 00 to 95.
Conversion does not start and
data becomes 0000.
Special I/O Unit Setting Error
The Special I/O Units registered
in the I/O table are different from
the ones actually mounted.
Bits
Functions
A50200
Unit #0 Restart Bit
Turning the Restart Bit for any
Unit ON and then OFF again
restarts that Unit.
A50201
Unit #1 Restart Bit
~
~
A50215
Unit #15 Restart Bit
A50300
Unit #16 Restart Bit
~
~
A50715
Unit #95 Restart Bit (See note.)
Probable cause
Countermeasure
Page
The input is not set for being used.
Set the input to be used.
The peak value hold function is in
operation.
Turn OFF the peak value hold func-
tion if it is not required.
The input device is not working, the
input wiring is wrong, or there is a
disconnection.
Using a tester, check to see if the
input voltage or current is changing.
---
Use Unit’s alarm flags to check for a
disconnection.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......