288
Specifications
Section 7-1
7-1
Specifications
7-1-1
Specifications
Note
1.
Refer to
on page 359 for details on the Unit’s di-
mensions.
2.
The maximum number of Analog I/O Units that can be mounted to one
Rack will varies depending on the Power Supply Unit model and the cur-
rent consumption of the other Units mounted to the Rack.
Input Specifications and Functions
Item
CJ1W-MAD42
Unit type
CJ-series Special I/O Unit
Isolation
Between I/O and PLC signals: Photocoupler
(No isolation between individual I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Current consumption
580 mA max. at 5 V DC
Dimensions (mm)
(See note 1.)
31 x 90 x 65 (W x H x D)
Weight
150 g max.
General specifications
Conforms to general specifications for SYSMAC CJ-series Series.
Mounting position
CJ-series CPU Rack or CJ-series Expansion Rack
(Cannot be mounted to a C200H Expansion I/O Rack or a SYSMAC BUS Slave Rack.)
Maximum number of Units
(See note 2.)
CPU Rack: 7 Units max.
Expansion Rack: 8 Units max.
Overall system:
(7 Units max. on CPU Rack) + (8 Units per Expansion Rack
×
3 Racks) = 31 Units max.
Data exchange with CPU
Units
Special I/O Unit Area CIO 200000 to CIO295915 (Words CIO 2000 to CIO 2959):
Exchanges 10 words of data per Unit.
Internal Special I/O Unit DM Area (D20000 to D29599)
Power Supply Units
Maximum number of Units
CJ1W-PA205R/PD025
CPU Rack: 7 Units max.
Expansion Racks: 8 Units/Rack max.
CJ1W-PA202
CPU Rack: 3 Units max.
Expansion Racks: 4 Units/Rack max.
Item
Voltage input
Current input
Number of analog inputs
4
Input signal range (See note
3.)
1 to 5 V
0 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
(See note 4.)
Maximum rated input (for 1
point) (See note 5.)
±
15 V
±
30 mA
External input impedance
1 M
Ω
min.
250
Ω
(rated value)
Resolution
4,000/8,000 (full scale) (See note 8.)
Converted output data
16-bit binary data
Accuracy
(See note 6.)
25
°
C
±
0.2% of full scale
0
°
C to 55
°
C
±
0.4% of full scale
A/D conversion time (See
note 7.)
1.0 ms/500
µ
s max. per point
Mean value processing
Stores the last “n” data conversions in the buffer, and stores the mean value of the conver-
sion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Peak value holding
Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......