171
Specifications
Section 5-1
Note
1.
Do not apply a voltage higher than 600 V to the terminal block when per-
forming withstand voltage test on this Unit.
2.
Refer to
Dimensions
on page 359 for details on the Unit’s dimensions.
3.
The maximum number of Analog Output Units that can be mounted to one
Rack varies depending on the current consumption of the other Units
mounted to the Rack.
Select a 24-VDC power supply based on the surge current. The following
OMRON power supplies are recommended.
S82K-05024: 100 VAC, 50 W
S82K-10024: 100 VAC, 100 W
S82J-5524: 100 VAC, 50 W
S82J-5024: 100 VAC, 100 W
4.
Data exchange methods with the CPU Unit are as follows:
5.
Output signal ranges can be set for each output.
6.
The accuracy is given for full scale. For example, an accuracy of
±
0.3%
means a maximum error of
±
12 (BCD) at a resolution of 4,000. For the
CJ1W-DA021/041, the accuracy is at the factory setting for a current out-
put. When using a voltage output, adjust the offset gain as required.
7.
D/A conversion time is the time required for converting and outputting the
PLC data. It takes at least one cycle for the data stored in the PLC to be
read by the Analog Output Unit.
8.
When the operation mode for the CPU Unit is changed from RUN mode or
MONITOR mode to PROGRAM mode, or when the power is turned ON,
the Output Conversion Enable Bit will turn OFF. The output status specified
according to the output hold function will be output.
9.
The CJ1W-DA08V/08C can be set to a conversion cycle of 250
µ
s and a
resolution of 8,000 using the setting in D(m+18).
Output hold
function
Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.
When the Conversion Enable Bit is OFF. (See note 8.)
In adjustment mode, when a value other than the output number is output during adjustment.
When there is an output setting error or a fatal error occurs at the PLC. (See note 10.)
When the CPU Unit is on standby.
When the Load is OFF.
Scaling function
Setting values in any specified unit within a range of
±
32,000 as the upper and lower limits allows D/A
conversion to be executed and analog signals to be output with these values as full scale.
(With the CJ1W-DA08V/DA08C, this function is enabled only for a conversion time of 1.0 s and a reso-
lution of 4,000.)
Item
CJ1W-DA021
CJ1W-DA041
CJ1W-DA08V
CJ1W-DA08C
Special I/O
Unit Area in
CIO Area
CIO 2000 to
CIO 2959
(CIO 200000
to CIO 295915
10 words per
Unit
Refreshed cycli-
cally
CPU Unit to
Analog I/O Unit
Analog output values
Conversion enable bits
Analog I/O Unit
to CPU Unit
Alarm flags
Special I/O
Unit Area in
DM Area
D20000 to
D29599
100 words per
Unit
Refreshed at
power ON and
restarts
CPU Unit to
Analog I/O Unit
Output signal conversion
settings and signal ranges
Output status when hold-
ing outputs
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......