218
Handling Errors and Alarms
Section 5-8
5-8-3
Errors in the CPU Unit
When errors occur in the CPU Unit or I/O bus, and I/O refresh with the Special
I/O Unit is not performed correctly resulting in the Analog Output Unit mal-
functioning, the ERH indicator will be lit.
ERH and RUN Indicators: Lit
The ERH and RUN indicators will be lit if an error occurs in the I/O bus caus-
ing a WDT (watchdog timer) error in the CPU Unit, resulting in incorrect I/O
refresh with the Analog Output Unit.
Turn ON the power supply again or restart the system.
For further details, refer to
CJ-series CJ1G-CPU
@@
,
CJ1G/H CPU
@@
H Pro-
grammable Controllers Operation Manual (W393)
.
Note
No error will be detected by the CPU Unit or displayed on the Programming
Console, because the CPU Unit is continuing operation.
ERH Indicator: Lit, RUN Indicator: Not Lit
The unit number for the Analog Output Unit has not been set correctly.
RUN
ERC
ERH
: Lit
: Not lit
Error
Error contents
Output condition
I/O bus error
Error has occurred during data
exchange with the CPU Unit.
Depends on the output hold func-
tion.
CPU Unit monitoring error (see
note)
No response from CPU Unit dur-
ing fixed period.
Maintains the condition just
before the error.
CPU Unit WDT error
Error has been generated in
CPU Unit.
Depends on the output hold func-
tion.
RUN
ERC
ERH
: Lit
: Not lit
Error
Error contents
Output condition
Duplicate Unit Number
The same unit number has been
assigned to more than one Unit
or the unit number was set to a
value other than 00 to 95.
The output value will be 0 V.
Special I/O Unit Setting Error
The Special I/O Units registered
in the I/O table are different from
the ones actually mounted.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......