102
Exchanging Data with the CPU Unit
Section 3-5
2.
If two or more Special I/O Units are assigned the same unit number, a
“UNIT No. DPL ERR” error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
Allocations for Normal
Mode
For normal mode, set the operation mode switch on the front panel of the Unit
as shown in the following diagram, or set bits 00 to 07 in DM word m+18.
The allocation of words and bits in the CIO Area is shown in the following
table.
CJ1W-AD041-V1
Note
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
CJ1W-AD081-V1
Note
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
O
N
12
MODE
OFF
OFF
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Not used.
Peak value hold
Input
4
Input
3
Input
2
Input
1
Input
(Unit to
CPU)
n + 1
Input 1 conversion value
16
3
16
2
16
1
16
0
n + 2
Input 2 conversion value
n + 3
Input 3 conversion value
n + 4
Input 4 conversion value
n + 5
Not used.
n + 6
Not used.
n + 7
Not used.
n + 8
Not used.
n + 9
Alarm Flags
Not used.
Disconnection detec-
tion
Input
4
Input
3
Input
2
Input
1
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Not used.
Peak value hold
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
Input
(Unit to
CPU)
n + 1
Input 1 conversion value
16
3
16
2
16
1
16
0
n + 2
Input 2 conversion value
n + 3
Input 3 conversion value
n + 4
Input 4 conversion value
n + 5
Input 5 conversion value
n + 6
Input 6 conversion value
n + 7
Input 7 conversion value
n + 8
Input 8 conversion value
n + 9
Alarm Flags
Disconnection detection
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......