256
Analog Input Functions and Operating Procedures
Section 6-6
the delay in the conversion data in comparison to changes in the input sig-
nals will be as shown in the following diagram.
2.
Specify “no mean value processing” to follow conversion of a rapid change
in input signals.
Response Time
Unit: ms
Symbols
m: Number of input words used in DM Area
n: Average number of buffers set for the input number for which to find the
response time
Calculation Example
The following example calculations are for a resolution of 8,000 with an appli-
cation using inputs 1 and 4, 64 averaging buffers set for input 1, and no aver-
aging set for input 4.
• Response time for input 1: t = {(64
−
2) x 2 + 10.5} = 134.5 (ms)
• Response time for input 1: t = 1 x (2 + 2) = 4 (ms)
Input signal
to the Unit (V)
Conversion data
Time (ms)
Time (ms)
t: Delay
For V = 20 V (
−
10 to 10 V)
Using One Word
t = n + (2 to 3)
Using m Words
(1
≤
m
≤
8)
No averaging (n = 1) or two averaging buffers (n = 2):
t = n x (m + 2)
n averaging buffers (4
≤
n
≤
64):
t = (n
−
2) x m + 10.5
m
n
64
32
16
8
4
2
1
4
258.5
130.5
66.5
34.5
18.5
12
6
3
196.5
100.5
52.5
28.5
16.5
10
5
2
134.5
70.5
38.5
22.5
14.5
8
4
1
67
35
19
11
7
5
3
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......