Exchanging Data with the CPU Unit
Section 4-5
DM Allocation Contents
The following table shows the allocation of DM words and bits for both normal
and adjustment mode.
CS1W-DA08V/08C
CS1W-DA041
Note
For the DM word addresses, m = (unit number x 100).
Set Values and Stored Values]
Note
1.
With the CS1W-DA041, the output signal ranges 1 to 5 V and 4 to 20 mA
are switched using the output terminal connections. For details, refer to
. With the CS1W-DA08C, these ranges are in-
valid. Regardless of the settings made, the output range will be 4 to 20 mA.
2.
The values output for the signal ranges will be 0 V for the range of
±
10 V,
and the minimum value for the other ranges. For details, refer to
.
DM word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
D(m)
Not used.
Output use setting
Out-
put 8
Out-
put 7
Out-
put 6
Out-
put 5
Out-
put 4
Out-
put 3
Out-
put 2
Out-
put 1
D(m+1)
Output signal range setting
Output 8
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
Output 1
D(m+2)
Not used.
Output 1: Output status when conversion stopped
D(m+3)
Not used.
Output 2: Output status when conversion stopped
D(m+4)
Not used.
Output 3: Output status when conversion stopped
D(m+5)
Not used.
Output 4: Output status when conversion stopped
D(m+6)
Not used.
Output 5: Output status when conversion stopped
D(m+7)
Not used.
Output 6: Output status when conversion stopped
D(m+8)
Not used.
Output 7: Output status when conversion stopped
D(m+9)
Not used.
Output 8: Output status when conversion stopped
DM word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
D(m)
Not used.
Not used.
Output use setting
Out-
put 4
Out-
put 3
Out-
put 2
Out-
put 1
D(m+1)
Not used.
Output signal range setting
Output 4
Output 3
Output 2
Output 1
D(m+2)
Not used.
Output 1: Output status when conversion stopped
D(m+3)
Not used.
Output 2: Output status when conversion stopped
D(m+4)
Not used.
Output 3: Output status when conversion stopped
D(m+5)
Not used.
Output 4: Output status when conversion stopped
Item
Contents
Page
Output
Use setting
0:
Not used.
1:
Used.
Output signal range
00:
–10 to 10 V
01:
0 to 10 V
10:
1 to 5 V/4 to 20 mA (See note 1.)
11:
0 to 5 V
Output status when stopped
00:
CLR
Outputs 0 or minimum value of each range.
(See note 2.)
01:
HOLD
Holds output just before stopping.
02:
MAX
Outputs maximum value of range.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......