349
Adjusting Offset and Gain
Section 7-9
Change the set value, using the Up Bit (bit 03 of word n+1) and the Down
Bit (bit 02 of word n+1).
• The following example increases the output voltage.
The bit will remain ON until the output voltage becomes an appropriate val-
ue, at which time, the output will turn OFF.
• The following example decreases the output voltage.
The bit will remain ON until the output voltage becomes an appropriate val-
ue, at which time, the output will turn OFF.
Up Bit
Down Bit
While the Up Bit is ON, the set value will be
increased by 1 resolution every 0.5 seconds.
After it has been ON for 3 seconds, the set
value will be increased by 1 resolution every
0.1 seconds.
While the Down Bit is ON, the set value will be
decreased by 1 resolution every 0.5 seconds.
After it has been ON for 3 seconds, the set
value will be decreased by 1 resolution every
0.1 seconds.
Word n+1
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Bit
SHIFT
CONT
#
2
C
0
A
0
A
1
B
0
A
3
D
MON
200103 ^ OFF
SET
200103 ^ ON
RESET
200103 ^ OFF
SHIFT
CONT
#
2
C
0
A
0
A
1
B
0
A
2
C
MON
200102 ^ OFF
SET
200102 ^ ON
RESET
200102 ^ OFF
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......