181
Operating Procedure
Section 5-2
2.
Set as required.
D00200 is set in word CIO 2011.
D00201 is set in word CIO 2012.
D00202 is set in word CIO 2013.
To start analog output, turn ON the
Conversion Enable Bits 201000 to
201002 (bits 00 to 03 of word
CIO 2010).
The data in words CIO 2011 and
2012 will be output as 1 to 5 V, and
CIO the data in CIO 2013 will be
output as –10 to 10 V.
MOV (021)
D00200
2011
MOV (021)
D00201
2012
Execution condition
MOV (021)
D00202
2013
SET
201000
SET
201002
SET
201001
Execution condition
for details.