240
Wiring
Section 6-4
6-3-4
Voltage/Current Switch
The analog conversion input can be switched from voltage input to current
input by changing the pin settings on the voltage/current switch located on the
back of the terminal block.
!Caution
Be sure to turn OFF the power to the PLC before mounting or removing the
terminal block.
6-4
Wiring
6-4-1
Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in
the following diagram.
Note
1.
The analog I/O numbers that can be used are set in the Data Memory
(DM).
2.
The I/O signal ranges for individual inputs and outputs are set in the Data
Memory (DM). They can be set in units of I/O numbers.
3.
The AG terminal (A8, B8) is connected to the 0-V analog circuit in the Unit.
Connecting shielded input lines can improve noise resistance.
4.
The N.C. terminals (A5, A11, B5) are not connected to internal circuitry.
IN2: Input 2
IN1: Input 1
OFF: Voltage input
ON: Current input
IN4: Input 4
IN3: Input 3
Output 2 (+)
B1
Output 2 (–)
B2
Output 4 (+)
B3
Output 4 (–)
B4
N.C.
B5
Input 2 (+)
B6
Input 2 (–)
B7
AG
B8
Input 4 (+)
B9
Input 4 (–)
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
Output 1 (+)
Output 1 (–)
Output 3 (+)
Output 3 (–)
N.C.
Input 1 (+)
Input 1 (–)
AG
Input 3 (+)
Input 3 (–)
N.C.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......