294
Specifications
Section 7-1
Range: 0 to 5 V
Range: –10 to 10 V
Note
The conversion values and set values for a range of –10 to 10 V will be as fol-
lows:
0000
(0000)
FF38
(FE70)
0FA0
(1F40)
1068
(20D0)
5.25 V
5 V
0 V
–0.25 V
Resolution: 4,000/8,000
Set value (16-bit binary data)
Analog output signal
( ): Values in parentheses are for a
resolution of 8,000.
0000
(0000)
F830
(F060)
F768
(EED0)
07D0
(0FA0)
0898
(1130)
0 V
–10 V
–11 V
11 V
10 V
Resolution: 4,000/8,000
Set value (16-bit binary data)
Analog output signal
( ): Values in parentheses are for a
resolution of 8,000.
16-bit binary data
BCD (Resolution: 4,000)
F768
–2200
:
:
FFFF
–1
0000
0
0001
1
:
:
0898
2200