291
Specifications
Section 7-1
7-1-3
Input Specifications
If signals that are outside the specified range provided below are input, the
conversion values used will be at either the maximum or minimum value.
Range: 1 to 5 V (4 to 20 mA)
Range: 0 to 10 V
1 V (4 mA)
0.8 V (3.2 mA)
5 V (20 mA)
5.2 V (20.8 mA)
Resolution: 4,000/8,000
Conversion value (16-bit binary data)
1068 (20D0)
0FA0 (1F40)
0000 (0000)
FF38 (FE70)
Analog input signal
( ): Values in parentheses are for a
resolution of 8,000.
0 V
10 V
–0.5 V
10.5 V
1068 (20D0)
0FA0 (1F40)
0000 (0000)
FF38 (FE70)
Resolution: 4,000/8,000
Conversion value (16-bit binary data)
Analog input signal
( ): Values in parentheses are for a
resolution of 8,000.
Summary of Contents for CJ1W-AD041-V1