346
Adjusting Offset and Gain
Section 7-9
Change the set value, using the Up Bit (bit 03 of word n+1) and the Down
Bit (bit 02 of word n+1).
• The following example increases the output voltage.
The bit will remain ON until the output becomes an appropriate value, at
which time, it will turn OFF.
• The following example decreases the output voltage.
The bit will remain ON until the output becomes an appropriate value, at
which time, it will turn OFF.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Bit
Up Bit
Down Bit
While the Up Bit is ON, the set value will be
increased by 1 resolution every 0.5 seconds.
After it has been ON for 3 seconds, the set
value will be increased by 1 resolution every
0.1 seconds.
While the Down Bit is ON, the set value will be
decreased by 1 resolution every 0.5 seconds.
After it has been ON for 3 seconds, the set
value will be decreased by 1 resolution every
0.1 seconds.
Word n+1
SHIFT
CONT
#
2
C
0
A
0
A
1
B
0
A
3
D
MON
200103 ^ OFF
SET
200103 ^ ON
RESET
200103 ^ OFF
SHIFT
CONT
#
2
C
0
A
0
A
1
B
0
A
2
C
MON
200102 ^ OFF
SET
200102 ^ ON
RESET
200102 ^ OFF
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......