208
Adjusting Offset and Gain
Section 5-7
Offset Adjustment
The procedure for adjusting the analog output offset is explained below. As
shown in the following diagram, the set value is adjusted so that the analog
output reaches the standard value (0 V/1 V/4 mA).
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1,2,3...
1.
Turn ON bit 00 (the Offset Bit) of CIO word n+1. (Hold the ON status.)
2.
Check whether the output devices are connected.
Note
The output is current output when using a CJ1W-DA08C.
3.
Monitor CIO word n+8 and check the set value while the Offset Bit is ON.
10 V
0
0FA0
Offset adjustment output range
Output signal range:
0 to 10 V
CLR
000000 CT00
SHIFT
CONT
#
2
C
0
A
0
A
1
B
0
A
0
A
MON
200100 ^ OFF
SET
200100 ^ ON
Voltage output (See note.)
Output 1
Current output (CJ1W-DA021/041 only)
CLR
000000 CT00
SHIFT
CH
*DM
2
C
0
A
0
A
8
MON
2008 0000