
75
Handling Errors and Alarms
Section 2-8
Value Does Not Change as Intended
Conversion Values are Inconsistent
Probable cause
Countermeasure
Page
The input device’s signal range
does not match the input signal
range for the relevant input number
at the Analog Input Unit.
Check the specifications of the
input device, and match the settings
for the input signal ranges.
The offset and gain are not
adjusted.
Adjust the offset and gain.
When using the 4 mA to 20 mA
range, the voltage/current switch is
not turned ON.
Turn ON the voltage/current switch.
Probable cause
Countermeasure
Page
The input signals are being affected
by external noise.
Change the shielded cable connec-
tion to the Unit’s COM terminal.
Insert a 0.01-
µ
F to 0.1-
µ
F ceramic
capacitor or film capacitor between
the input’s (+) and (–) terminals.
---
Try increasing the number of mean
value processing buffers.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......