130
Operating Procedure
Section 4-2
Range:
−
10 to 10 V
Note
The set values for a range of –10 to 10 V will be as follows:
4-2
Operating Procedure
Follow the procedure outlined below when using Analog Output Units.
Installation and Settings
1,2,3...
1.
Set the operation mode switch on the rear panel of the Unit to normal
mode.
2.
Wire the Unit.
3.
Use the unit number switch on the front panel of the Unit to set the unit
number.
4.
Turn ON the power to the PLC.
5.
Create the I/O tables.
6.
Make the Special I/O Unit DM Area settings.
• Set the output numbers to be used.
• Set the output signal ranges.
• Set the output hold function.
7.
Turn the power to the PLC OFF and ON, or turn ON the Special I/O Unit
Restart Bit.
When the output for the connected devices needs to be calibrated, follow the
procedures in
Offset and Gain Adjustment
below. Otherwise, skip to
Opera-
tion
below.
0000
F830
F768
07D0
0898
0 V
–10 V
–11 V
11 V
10 V
Resolution: 4,000
Set value (16-bit binary data)
Analog output signal
16-bit binary data
BCD
F768
–2200
:
:
FFFF
–1
0000
0
0001
1
:
:
0898
2200
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......