
300
Operating Procedure
Section 7-2
b)
Set as required.
c)
The input Disconnection Detection Flag is allocated to bits 04 to
07 of word (n + 9). Refer to
7-6-6 Input Disconnection Detection Function
for
further details.
2.
The following example shows how to use analog outputs.
The setting address D00200 is stored in words (n+1) to (n+2) of the Special I/
O Unit Area (CIO 2011 to CIO 2012) as a signed binary value between 0000
to 0FA0 hex.
• The following table shows the addresses used for analog output.
Note a)
The addresses are set according to the unit number of the Special
I/O Unit. Refer to
for further details.
201904 Input 1 Disconnection Detection Flag (See note c.)
Always ON Flag
201906 Input 3 Disconnection Detection Flag (See note c.)
201907 Input 4 Disconnection Detection Flag (See note c.)
For 1 to 5 V, the hexadecimal value 0000
to 0FA0 will be stored in CIO 2015, so if
there is no disconnection (i.e., 201904 is
OFF), CIO 2015 will be stored in
D00100.
In the same way, for 0 to 10 V, CIO 2016
will be stored in D00101.
In the same way, for 4 to 20 mA, CIO 2017
will be stored in D00102.
In the same way, for 4 to 20 mA, CIO 2018
will be stored in D00103.
MOV (021)
2015
D00100
MOV (021)
2016
D00101
MOV (021)
2017
D00102
MOV (021)
2018
D00103
The disconnection detection function is not
valid for the 0 to 10-V range, so the
Disconnection Detection Flag cannot be
used.
Output number
Input signal range
Output setting
address
(n = CIO 2010)
See note 1.
Original
conversion
address
1
0 to 10 V
(n+1) = CIO 2011
D00200
2
4 to 20 mA
(n+2) = CIO 2012
D00201
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......