179
Operating Procedure
Section 5-2
• The following diagram shows the output settings used. Refer to
Output Settings and Conversions
for more details.
• The following diagram shows the output range settings. Refer to
Output Settings and Conversions
for more details.
Note
The output range setting is not required for the CJ1W-DA08C.
• The following diagram shows the conversion time/resolution setting for
the DA08V. (Refer to
5-6-2 Conversion Time/Resolution Setting
2.
Turn OFF the external power supply.
3.
Restart the CPU Unit.
4.
Turn ON the external power supply.
15
14 13
12 11 10
09 08 07
06 05
01 00
04 03
02
0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1
Bit
Not used
Output 4
Output 3
Output 2
Output 1
Used
m: DM20100
(0007 Hex)
15
14 13
12 11 10
09 08 07
06 05
01 00
04 03
02
0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0
Bit
m+1: DM20101
(000A Hex)
Output 1: 1 to 5 V. Set to 10.
Output 2: 1 to 5 V. Set to 10.
Output 3: –10 to 10 V. Set to 00.
Output 4: Not used. Set to 00 (disabled).
15
14
13
12
11
10
09
08
07
06
05
01
00
04
03
02
0 0 0 0 0 0 0 0
Bit
m+18: D20118
(0000 Hex)
Conversion Time/Resolution Setting
0000: 1-ms conversion time, 4,000 resolution
C100: 250-
µ
s conversion time, 8,000 resolution
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......