78
Specifications
Section 3-1
3-1
Specifications
3-1-1
Specifications
Note
1.
Do not apply a voltage higher than 600 V to the terminal block when per-
forming withstand voltage test on this Unit. Otherwise, internal elements
may deteriorate.
2.
Refer to
Dimensions
on page 359 for details on the Unit’s dimensions.
Item
CJ1W-AD041-V1
CJ1W-AD081-V1
Unit type
CJ-series Special I/O Unit
Isolation (See note 1.)
Between I/O and PLC signals: Photocoupler
(No isolation between individual I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Affect on CPU Unit cycle time
0.2 ms
Power consumption
420 mA max. at 5 VDC
Dimensions (mm) (See note 2.)
31 x 90 x 65 (W x H x D)
Weight
140 g max.
General specifications
Conforms to general specifications for SYSMAC CJ Series.
Mounting position
CJ-series CPU Rack or CJ-series Expansion Rack
Maximum number of Units (See note 3.)
Units per Rack (CPU Rack or Expansion Rack): 4 to10 Units max. (See note
3.)
Data exchange with CPU Units
(See note 4.)
Special I/O Unit Area in CIO Area (CIO 2000 to CIO 2959): 10 words per Unit
Special I/O Unit Area in DM Area (D20000 to D29599): 100 words per Unit
Inputs
specifica-
tions
Number of analog inputs
4
8
Input signal range
(See note 5.)
1 to 5 V
0 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
(See note 6.)
Maximum rated input (for 1
point) (See note 7.)
Voltage Input:
±
15 V
Current Input:
±
30 mA
Input impedance
Voltage Input: 1 M
Ω
min.
Current Input: 250
Ω
(rated value)
Resolution (See note 8.)
4,000/8,000
4,000/8,000
Converted output data
16-bit binary data
Accuracy
(See note 9.)
23
±
2
°
C
Voltage Input:
±
0.2% of full scale
Current Input:
±
0.4% of full scale
0
°
C to 55
°
C Voltage Input:
±
0.4% of full scale
Current Input:
±
0.6% of full scale
A/D conversion time
(See note 10.)
1 ms/250
µ
s
(See note 8.)
1 ms/250
µ
s
(See note 8.)
Inputs func-
tions
Mean value processing
Stores the last “n” data conversions in the buffer, and stores the mean value of
the conversion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Peak value holding
Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Input disconnection detec-
tion
Detects the disconnection and turns ON the Disconnection Detection Flag.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......