48
Exchanging Data with the CPU Unit
Section 2-5
CS1W-AD041-V1
Note
For the CIO word addresses, n = CIO 2000 + unit number x 10.
CS1W-AD081-V1
Note
For the CIO word addresses, n = CIO 2000 + unit number x 10.
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Not used.
Peak value hold
Input
4
Input
3
Input
2
Input
1
Input
(Unit to
CPU)
n + 1
Input 1 conversion value
16
3
16
2
16
1
16
0
n + 2
Input 2 conversion value
n + 3
Input 3 conversion value
n + 4
Input 4 conversion value
n + 5
Not used
n + 6
Not used
n + 7
Not used
n + 8
Not used
n + 9
Alarm Flags
Not used
Disconnection
detection
Input
4
Input
3
Input
2
Input
1
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Not used.
Peak value hold
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
Input
(Unit to
CPU)
n + 1
Input 1 conversion value
16
3
16
2
16
1
16
0
n + 2
Input 2 conversion value
n + 3
Input 3 conversion value
n + 4
Input 4 conversion value
n + 5
Input 5 conversion value
n + 6
Input 6 conversion value
n + 7
Input 7 conversion value
n + 8
Input 8 conversion value
n + 9
Alarm Flags
Disconnection detection
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......