24
Operating Procedure
Section 2-2
Initial Data Settings
1,2,3...
1.
Specify the Special I/O Unit DM Area settings. Refer to
for further details.
• The following diagram shows the input settings used. Refer to
DM Al-
location Contents
2-6-1 Input Settings and Conversion
• The following diagram shows the input range settings. Refer to
DM Al-
location Contents
2-6-1 Input Settings and Conversion
Also set DM word m+52 when using current input with the CS1W-AD161.
Peripheral port
Setting conditions
Unit No. 1
Analog input 1: 1 to 5 V
Analog input 2: 1 to 5 V
Analog input 3: 4 to 20 mA
Analog input 4: 4 to 20 mA
Analog input 5: 0 to 10 V
Analog input 6: 0 to 10 V
Analog input 7: –10 to 10 V
Analog input
8: Not used.
15
14
13
12
11
10
09
08
07
06
05
01
00
04
03
02
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1
Bit
Input 4
Input 3
Input 2
Input 1
Used
m: D20100
(007F Hex)
Not used
Input 8
Input 7
Input 6
Input 5
15
14
13
12
11
10
09
08
07
06
05
01
00
04
03
02
0 0 0 0 0 1 0 1 1 0 1 0 1 0 1 0
Bit
m+1: D20101
(05AA Hex)
Input 1: 1 to 5 V. Set to 10.
Input 2: 1 to 5 V. Set to 10.
Input 3: 4 to 20 mA. Set to 10.
Input 4: 4 to 20 mA. Set to 10.
Input 5: 0 to 10 V. Set to 01.
Input 6: 0 to 10 V. Set to 01.
Input 7:
−
10 to 10 V. Set to 00.
Input 8: Not used. Set to 00 (disabled)
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......