142
Exchanging Data with the CPU Unit
Section 4-5
4-4-4
Output Wiring Considerations
When wiring outputs, apply the following points to avoid noise interference
and optimize Analog Output Unit performance.
• Use two-core shielded twisted-pair cables for output connections.
• Route output cables separately from the AC cable, and do not run the
Unit’s cables near a main circuit cable or a high voltage cable. Do not
insert output cables into the same duct.
• If there is noise interference from power lines (if, for example, the power
supply is shared with electrical welding devices or electrical discharge
machines, or if there is a high-frequency generation source nearby) install
a noise filter at the power supply input area.
4-5
Exchanging Data with the CPU Unit
4-5-1
Outline of Data Exchange
Data is exchanged between the CPU Unit and the CS1W-DA08V/08C/041
Analog Output Unit via the Special I/O Unit Area (for data used to operate the
Unit) and the Special I/O Unit DM Area (for data used for initial settings).
I/O Refresh Data
Analog output setting values and other data used to operate the Unit are allo-
cated in the Special I/O Unit Area of the CPU Unit according to the unit num-
ber, and are exchanged during I/O refreshing.
Fixed Data
The Unit’s fixed data, such as the analog output signal ranges and the output
status when conversion is stopped, is allocated in the Special I/O Unit DM
Area of the CPU Unit according to the unit number, and is exchanged when
the power is turned ON or the Unit is restarted.
CS-series CPU Unit
CS1W-DA08V/08C/041 Analog Output Unit
Special I/O Unit Area
I/O Refresh Data
Analog outputs
DM (Data Memory) Area
Analog output
ranges
Output status
when conversion
stopped
I/O refresh
Power ON or
Unit restart
Exchanges analog output
values exchanged during
data refresh.
Transmits fixed data such
as conversion stop values
and analog output ranges.
2000 + n x 10
2000 + n x 10 + 9
n x 100
n x 100 + 99
10
words
100
words
Fixed Data
:
:
n: Unit number
page 147 for
details.
See
on
page 145 for
details.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......