98
Exchanging Data with the CPU Unit
Section 3-5
3-5-2
Unit Number Settings
The Special I/O Unit Area and Special I/O Unit DM Area word addresses that
each Analog Input Unit occupies are set by the unit number switch on the front
panel of the Unit.
Note
If two or more Special I/O Units are assigned the same unit number, a “UNIT
No. DPL ERR” error (in the Programming Console) will be generated (A40113
will turn ON) and the PLC will not operate.
3-5-3
Special I/O Unit Restart Bits
To restart the Unit operations after changing the contents of the data memory
or correcting an error, turn ON the power to the PLC again or turn the Special
I/O Unit Restart Bit ON and then OFF again.
Note
If the error is not corrected by restarting the Unit or turning the Special I/O
Unit Restart Bit ON and then OFF again, replace the Analog Input Unit.
Switch
setting
Unit
number
Special/O Unit Area
addresses
Special I/O Unit DM Area
addresses
0
Unit #0
CIO 2000 to CIO 2009
D20000 to D20099
1
Unit #1
CIO 2010 to CIO 2019
D20100 to D20199
2
Unit #2
CIO 2020 to CIO 2029
D20200 to D20299
3
Unit #3
CIO 2030 to CIO 2039
D20300 to D20399
4
Unit #4
CIO 2040 to CIO 2049
D20400 to D20499
5
Unit #5
CIO 2050 to CIO 2059
D20500 to D20599
6
Unit #6
CIO 2060 to CIO 2069
D20600 to D20699
7
Unit #7
CIO 2070 to CIO 2079
D20700 to D20799
8
Unit #8
CIO 2080 to CIO 2089
D20800 to D20899
9
Unit #9
CIO 2090 to CIO 2099
D20900 to D20999
10
Unit #10
CIO 2100 to CIO 2109
D21000 to D21099
~
~
~
~
n
Unit #n
CIO 2000 + (n x 10) to
CIO 2000 + (n x 10) + 9
(n x 100) to
(n x 100) + 99
~
~
~
~
95
Unit #95
CIO 2950 to CIO 2959
D29500 to D29599
MACH
No
.
10
1
10
0
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
Special I/O Unit
Area word
address
Function
A50200
Unit No. 0 Restart Bit
Restarts the Unit when turned
ON and then OFF again.
A50201
Unit No. 1 Restart Bit
~
~
A50215
Unit No. 15 Restart Bit
A50300
Unit No. 16 Restart Bit
~
~
A50715
Unit No. 95 Restart Bit
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......