313
Exchanging Data with the CPU Unit
Section 7-5
DM Allocation Contents
The following table shows the allocation of DM words and bits for both normal
and adjustment mode.
DM word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
D(m)
Ratio conversion use setting
Input use setting
Output use setting
Not used.
Not used.
Loop 2
Loop 1
Input
4
Input
3
Input
2
Input
1
Not
used.
Not
used.
Out-
put 2
Out-
put 1
D(m+1)
Input signal range setting
Output signal range setting
Input 4
Input 3
Input 2
Input 1
Not used.
Not used.
Output 2
Output 1
D(m+2)
Not used.
Output 1: Output status when conversion stopped
D(m+3)
Not used.
Output 2: Output status when conversion stopped
D(m+4)
Not used.
D(m+5)
Not used.
D(m+6)
Input 1: Mean value processing setting
D(m+7)
Input 2: Mean value processing setting
D(m+8)
Input 3: Mean value processing setting
D(m+9)
Input 4: Mean value processing setting
D(m+10)
Loop 1 (input 1 to output 1), A constant
D(m+11)
Loop 1 (input 1 to output 1), B constant
D(m+12)
Loop 2 (input 2 to output 2), A constant
D(m+13)
Loop 2 (input 2 to output 2), B constant
D(m+14)
Not used.
D(m+15)
Not used.
D(m+16)
Not used.
D(m+17)
Not used.
D(m+18)
Conversion time and resolution setting
Operation mode setting
D(m+19)
Output 1 scaling lower limit (Enabled only for conversion time of 1 ms and resolution of 4,000.)
D(m+20)
Output 1 scaling upper limit (Enabled only for conversion time of 1 ms and resolution of 4,000.)
D(m+21)
Output 2 scaling lower limit (Enabled only for conversion time of 1 ms and resolution of 4,000.)
D(m+22)
Output 2 scaling upper limit (Enabled only for conversion time of 1 ms and resolution of 4,000.)
D(m+23)
Not used.
D(m+24)
Not used.
D(m+25)
Not used.
D(m+26)
Not used.
D(m+27)
Input 1 scaling lower limit
D(m+28)
Input 1 scaling upper limit
D(m+29)
Input 2 scaling lower limit
D(m+30)
Input 2 scaling upper limit
D(m+31)
Input 3 scaling lower limit
D(m+32)
Input 3 scaling upper limit
D(m+33)
Input 4 scaling lower limit
D(m+34)
Input 4 scaling upper limit
D(m+35)
Voltage/current range setting (Enabled only when set for 1 to 5 V, 4 to 20 mA)
Not used.
Input
4
Input
3
Input
2
Input
1
Not used.
Out-
put 2
Out-
put 1
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......