Analog Input Functions and Operating Procedures
Section 2-6
Setting 0: Not used (the conversion value is reset when the bit turns OFF)
1: Peak value hold function is used (held while ON)
• CS1W-AD041-V1: Inputs 1 to 4
• CS1W-AD081-V1: Inputs 1 to 8
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
In the following example, the peak value hold function is in effect for input
number 1, and the unit number is 0.
When mean value processing is used together with the peak value hold func-
tion, the mean value will be held.
As long as the peak value hold function is in effect, the peak value hold will be
held even in the event of a disconnection.
When the load to the CPU Unit is disconnected, the Peak Value Hold Bits.
2-6-5
Input Disconnection Detection Function
When an input signal range of 1 to 5 V (4 to 20 mA) is used, input circuit dis-
connections can be detected. The detection conditions for each of the input
signal ranges are shown in the following table. (see note)
Note
The current/voltage level will fluctuate according to the offset/gain adjustment.
The following bits turn ON when a disconnection is detected in each input.
When the connection is recovered, these bits turn OFF. Be sure to specify
these bits in the execution condition of the ladder program when using the dis-
connection detection function in the user program.
CS1W-AD041-V1/AD081-V1
CS1W-AD041-V1: Inputs 1 to 4
CS1W-AD161
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
The conversion value during a disconnection will be 0000.
200000
Input condition
The maximum
conversion
data value is
held for input
number 1.
Range
Current/voltage
1 to 5 V
0.3 V max.
4 to 20 mA
1.2 mA max.
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
n = 2000 + unit number x 10
Word n+9
Not used.
Input 6
Input 5
Input 8
Input 7
Input 2
Input 1
Input 4
Input 3
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
n = 2000 + unit number x 10
Input 2
Input 1
Input 4
Input 3
Input 6
Input 5
Input 8
Input 7
Input 10
Input 9
Input 12
Input 11
Input 14
Input 13
Input 16
Input 15
Word n+18
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......