322
Analog Input Functions and Operating Procedures
Section 7-6
4.
With the fourth cycle, the Data 4 is stored in the first history buffer.
Mean value = (Data 4 + Data 3 + Data 2 + Data 1)
÷
4
5.
With the fifth cycle, Data 5 is stored in the first history buffer.
Mean value = (Data 5 + Data 4 + Data 3 + Data 2)
÷
4
When a disconnection is restored, the mean value processing function begins
again from step 1.
Note
1.
When the mean value processing function is used, the delay in refreshing
converted data for input signal changes will be as shown in the following
diagram.
2.
Specify “no mean value processing” to follow conversion of a rapid change
in input signals.
Response Time for a
Resolution of 1 ms/4,000
Unit: ms
(Mean value
processing)
Conversion value
Data 4
Data 3
Data 2
Data 1
(Mean value
processing)
Conversion value
Data 5
Data 4
Data 3
Data 2
Input signal
to the Unit (V)
Conversion data
Time (ms)
Time (ms)
t: Delay
For V = 20 V (
−
10 to 10 V)
When Resolution is 1 ms/4,000
•
For One Word
t = n + (2 to 3)
•
For m Words (1 < m
≤
4)
No averaging (n = 1) or two averaging buffers (n = 2)
t = n
×
(m + 2)
For n averaging buffers (4
≤
n
≤
64)
t = (n
−
2)
×
m + 10.5
When Resolution is 500
µ
s/8,000
•
For One Word
t = [n + (2 to 3)]
×
1/4
•
For m Words (1 < m
≤
4)
No averaging (n = 1) or two averaging buffers (n = 2)
t = n
×
(m + 2)
×
1/2
For n averaging buffers (4
≤
n
≤
64)
t = [(n
−
2)
×
m + 10.5]
×
1/2
m
n
64
32
16
8
4
2
1
4
258.5
130.5
66.5
34.5
18.5
12
6
3
196.5
100.5
52.5
28.5
16.5
10
5
2
134.5
70.5
38.5
22.5
14.5
8
4
1
67
35
19
11
7
5
3
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......