180
Operating Procedure
Section 5-2
Creating Ladder Programs
The setting address D00200 is stored in words (n + 1) to (n + 3) of the Special
I/O Unit Area (CIO 2011 to CIO 2013) as a signed binary value between 0000
to 0FA0 Hex.
The following table shows the addresses used for analog output.
Note
1.
The addresses are set according to the unit number of the Special I/O Unit.
Refer to
for further details.
Output number
Output signal
range
Output setting
address
(n = CIO 2010)
See note 1.
Original
conversion
address
1
1 to 5 V
(n+1) = CIO 2011
D00200
2
0 to 10 V
(n+2) = CIO 2012
D00201
3
–10 to 10 V
(n+3) = CIO 2013
D00202
4
Not used.
---
---
OD261
SYSMAC
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
RUN
ERR/ALM
INH
PRPHL
COMM
OPEN
PERIHERAL
PORT
MCPWR
BUSY
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
20
1
CN1
DC24V 0.3A
1
20
CN2
B/A
A/B
0
1
2
3
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
AD081
B1
A1
MACH
No.
x10
1
x10
0
RUN
ERC
ERH
ADJ
MODE
12
DA041
B1
A1
MACH
No.
x10
1
x10
0
RUN
ERC
ERH
ADJ
MODE
12
Peripheral port
Programming Console
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......