141
Wiring
Section 4-4
4-4-3
Output Wiring Example
Note
Crimp-type terminals must be used for terminal connections, and the screws
must be tightened securely. Use M3 screws and tighten them to a torque of
0.5 N·m.
To minimize output wiring noise, ground the output signal line to the input
device.
Output 2
CS1W-DA08V/08C
Shield
Output 4
Output 6
Output 8
Shield
Output 1
Output 3
Output 5
Output 7
Output 2
(Voltage output)
Output 4
(Current output)
CS1W-DA041
Output 3
(Current output)
Output 1
(Voltage output)
6.0 mm max.
6.0 mm max.
M3 screw
Fork type
Round type