Chapter 13 Control Sub Functions
[3] Setting method
To use the "stop command processing for deceleration stop function", set the
following control data in a sequence program.
The set data are made valid as soon as they are written to the buffer memory.
The PLC ready signal [Y0] is irrelevant.
Setting item
Setting
value
Setting details
Buffer memory address
[Cd.42]
Stop command
processing for
deceleration stop
selection
Set the stop command processing for
deceleration stop function.
0: Deceleration curve re-processing
1: Deceleration curve continuation
5907
: For details of the setting details, refer to Section 5.7 "List of control data".