13 - 60
Chapter 13 Control Sub Functions
[1] Control details
The torque value (forward new torque value/new reverse torque value) of the
axis control data can be changed at all times. The torque can be limited with a
new torque value from the time the new torque value has been written to the
Simple Motion module.
Note that the delay time until a torque control is executed is max. operation cycle
after torque change value was written.
The toque limiting is not carried out from the time the power supply is turned ON
to the time the PLC READY signal [Y0] is turned ON.
The new torque value ([Cd.22], [Cd.113]) is cleared to zero at the leading edge
(OFF to ON) of the positioning start signal [Y10].
The torque setting range is from 0 to "[Pr.17] Torque limit setting value".
(When the setting value is 0, a torque change is considered not to be carried out,
and it becomes to the value set in "[Pr.17] Torque limit setting value" or "[Cd.101]
Torque output setting value".)
The torque change range is 1 to "[Pr.17] Torque limit setting value".
The following drawing shows the operation at the same setting (Figure 13.31)
and the operation at the individual setting (Figure 13.32) for the forward new
torque value and new reverse torque value.
Each operation
PLC READY signal [Y0]
All axis servo ON [Y1]
Positioning start
signal [Y10]
Torque limit setting
value
Torque output setting
value
New torque value/ forward
new torque value
Torque limit stored value/
forward torque limit
stored value
Pr.17
Cd.101
Cd.22
Md.35
1
300
250
0
100
150
0
200
0
350
0
75
230
0
0
300
300
200
100
75
230
150
1
2
2
2
3
3
4
4
4
4
4
3
6
5
1: The torque limit setting value or torque output setting value becomes effective at the PLC READY signal [Y0] rising edge
(however, after the servo turned ON.)
If the torque output setting value is "0" or larger than the torque limit setting value, the torque limit setting value will be its value.
2: The torque limit setting value or torque output setting value becomes effective at the positioning start signal [Y10] rising edge,
and the torque limit value is updated.
If the torque output setting value is "0" or larger than the torque limit setting value, the torque limit setting value will be its value.
3: The torque change value is cleared to "0" at the positioning start signal [Y10] rising edge.
4: The torque limit value is changed by the torque changed value.
5: When the new torque value is 0, a torque change is considered not to be carried out.
6: When the change value is exceeds the torque limit value, a torque change is considered not to be carried out.
Torque change function
switching request
Cd.112
0
Fig. 13.31 Torque change operation (forward/reverse torque limit value same setting) (Axis 1)
Summary of Contents for MELSEC Q Series
Page 2: ......
Page 30: ...A 28 MEMO ...
Page 32: ...MEMO ...
Page 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Page 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Page 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Page 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Page 376: ...MEMO ...
Page 400: ...8 24 Chapter 8 HPR Control MEMO ...
Page 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Page 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Page 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Page 586: ...11 32 Chapter 11 Manual Control MEMO ...
Page 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Page 830: ...Appendix 30 Appendices MEMO ...
Page 833: ......