4 - 11
Chapter 4 Installation, Wiring and Maintenance of the Product
[Wiring example of shielded cable]
The following shows a wiring example for noise reduction in the case when the
connector (LD77MHIOCON) is used.
To Simple Motion module
Connector
(LD77MHIOCON)
The shield must be grounded in the cable connector shell.
For manual pulse generator
/incremental synchronous encoder input signal
For forced stop input signal
/External command signal/Switching signal
Shielded cable
[Processing example of shielded cables]
Connections of FG wire and each shielded cable
Wrap the coated part with a heat
contractile tube.
Remove the covering from all shielded
cables and bind the appeared shield
with a conductive tape.